View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 9.4
ATTENTION: Exploitable from adjacent network/Low attack complexity
Vendor: IOSiX
Equipment: IO-1020 Micro ELD
Vulnerabilities: Use of Default Credentials, Download of Code Without Integrity Check

2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an adjacent attacker to take control of vehicle systems by connecting to and modifying the affected device.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following IOSiX products are affected:

IO-1020 Micro ELD: Versions prior to 360

3.2 Vulnerability Overview
3.2.1 USE OF DEFAULT CREDENTIALS CWE-1392
IO-1020 Micro ELD uses a default WIFI password that could allow an adjacent attacker to connect to the device.
CVE-2024-30210 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.4 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N).
A CVSS v4 score has also been calculated for CVE-2024-30210. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:H/SI:H/SA:H).
3.2.2 USE OF DEFAULT CREDENTIALS CWE-1392
Web server uses a default password for authentication.
CVE-2024-31069 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.4 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N).
A CVSS v4 score has also been calculated for CVE-2024-31069. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:H/SI:H/SA:H).
3.2.3 DOWNLOAD OF CODE WITHOUT INTEGRITY CHECK CWE-494
IO-1020 Micro ELD downloads source code or an executable from an adjacent location and executes the code without sufficiently verifying the origin or integrity of the code.
CVE-2024-28878 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.6 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-28878. A base score of 9.4 has been calculated; the CVSS vector string is (CVSS4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Transportation
COUNTRIES/AREAS DEPLOYED: North America
COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER
Jake Jepson of Colorado State University reported these vulnerabilities to CISA.
4. MITIGATIONS
IOSIX recommends users update to 360.
For further support, contact IOSiX.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.
5. UPDATE HISTORY

April 2, 2024: Initial Publication

https://www.cisa.gov/news-events/ics-advisories/icsa-24-093-01