A vulnerability is reported in WIBU-SYSTEMS Codemeter. WIBU-SYSTEMS Codemeter is installed by default during e!COCKPIT and WAGO-I/O-Pro (CODESYS 2.3) installations. All currently existing e!COCKPIT installation bundles and WAGO-I/O-Pro (CODESYS 2.3) installation bundles are affected with vulnerable versions of WIBU-SYSTEMS Codemeter.



Apache Log4j is used for logging events in WAGO Smart Script in Version 4.2 and higher.  Events logged by Log4j can contain JNDI references. An attacker who can control log messages or log message parameters can execute arbitrary code loaded from LDAP servers when message lookup substitution is enabled. Additionally, Log4j does not protect from self-referential lookups, which can lead to Denial of Service.

UPDATE A1/2: 
Affected versions:

CVE-2021-44228 and CVE-2021-45046:
WAGO Smart Script >= Version 4.2 and < Version 4.8.1.3

CVE-2021-45105:
WAGO Smart Script >= Version 4.2 and < Version 4.8.1.4

CVE-2021-44832
WAGO Smart Script >= Version 4.2 and < Version 4.8.1.5

END UPDATE A1/2



Multiple vulnerabilities were reported in CODESYS 2.3 Runtime. The CODESYS 2.3 Runtime is an essential component in several WAGO PLCs. All vulnerable PLCs are listed in chapter ‘Affected Products’.
https://www.codesys.com/security/security-reports.html



A Denial-of-Service Vulnerability was reported in CODESYS 2.3 Runtime. The CODESYS 2.3 Runtime is an essential component in several WAGO PLC’s. All vulnerable PLCs are listed in chapter ‘Affected Products’.
https://www.codesys.com/security/security-reports.html



Multiple vulnerabilities were reported in the Nucleus Real-Time Operating System (RTOS). The Nucleus RTOS is an essential component in several WAGO PLCs and fieldbus coupler. WAGO uses older Versions of the Nucleus RTOS also in legacy products.

For additional information please consult the official Siemens advisory:

• Advisory SSA-044112



Multiple vulnerabilities were reported in WIBU-SYSTEMS Codemeter. WIBU-SYSTEMS Codemeter is installed by default during e!COCKPIT and WAGO-I/O-Pro (CODESYS 2.3) installations. All currently existing e!COCKPIT installation bundles and WAGO-I/O-Pro (CODESYS 2.3) installation bundles with Version 2.3.9.46, 2.3.9.47, 2.3.9.49, 2.3.9.53, 2.3.9.55, 2.3.9.61 and 2.3.9.66 contain vulnerable versions of WIBU-SYSTEMS Codemeter.



The Web-Based Management (WBM) of WAGOs programmable logic controller (PLC) is typically used for administration, commissioning and updates.
With special crafted requests it is possible to read and write some special parameters without authentication.
This vulnerability is different to advisory SAV-2020-014 / VDE-2020-028.



WAGO: OpenSSL DoS Vulnerability in PLCs

WAGO controllers have always been designed for easy connection to IT infrastructure. Even controllers from legacy product lines support encryption standards to ensure secure communication.
With special crafted requests it is possible to bring the device out of operation.
All listed devices are vulnerable for this denial of service attack.